KMAY32 MODULE TO CONNECT 32 DETECTORS / 10 ALARM CALL POINTS
Microprocessed and algorithmic-addressable module (with short-circuit insulator) which is installed as one more element in the loop.
This module allows the connection of conventional detectors and/or alarm call points in an algorithmic-addressable fire detection system, performing the interface function between an algorithmic-addressable control panel and a conventional system. Up to a maximum of 10 conventional alarm call points can be installed on the strip of “Area C”. The “D Area” strip allows a maximum of 32 temperature detectors (A30XT, A30XV) or 32 components between smoke detectors (A30XH, A30XHS) and conventional alarm call points. Both strips supervise the line using a 4K7 end-of-line resistor. It thus indicates the status of the open line, crossed line, detector alarm or alarm call point alarm.