Cylindrical cased axial flow fans
THGT Series
Cased axial flow fans designed for smoke extract in fire conditions and certified F400-120, F300/F200-120 to EN 12101-3 (CE marked).
Casings formed from rolled sheet steel with a corrosion resistant hot dip galvanised finish to EN 1461. Corrosion category C4.
Variable pitch angle impeller, dynamically balanced to ISO 14694: G6.3, made from high grade aluminum. Hubs made from aluminium or pressed sheet steel, depending on diameter and mechanical requirements.
2 Poles F400-120 model with aluminium impeller-hub formed from a one piece casting.
All models are available in both short and long casing versions except 2 poles F400-120 model only supplied with long casing.
Standard air operation temperature range: -20ºC to +40ºC.